Adding helper method in RADIUS packet
Starting snapshot 2.2.7-SNAPSHOT
Case 5: Bridging test between two untagged hosts on vlan-untagged port, with single ToR, ovs switches and 3 ONOS instances - PASS
...
- 37.1 Apply cell to environment - PASS
- 37.2 Uninstalling Atomix - PASS
- 37.3 Uninstalling ONOS package - PASS
- 37.4 Installing Atomix - PASS
- 37.5 Installing ONOS package - PASS
- 37.6 Set up ONOS secure SSH - PASS
- 37.7 Checking ONOS service - PASS
- 37.8 Starting ONOS CLI sessions - PASS
- 37.9 Checking ONOS nodes - PASS
- 37.10 Checking ONOS applications - PASS
- 37.11 Set logging levels - PASS
- 37.12 Set ONOS configurations - PASS
- 37.13 Starting Mininet Topology - PASS
- 37.14 Check whether the flow count is bigger than 74 - PASS
- 37.15 Check whether all flow status are ADDED - FAIL Flow status is wrong!
- PASS
- 37.16 Check whether the flow count of device of:0000000000000001 is bigger than 37 - PASS
- 37.17 Check whether the flow count of device of:0000000000000002 is bigger than 37 - PASS
- 37.18 Verify full connectivity for [u'h1', u'h2'] with tag CASE37 - PASS FAIL
- IP connectivity failed
- 37.19 Verify full connectivity for [u'h3', u'h4'] with tag CASE37 - PASS
- 37.20 Stopping Mininet - PASS
- 37.21 Copying karaf logs - PASS
...
- 46.1 Apply cell to environment - PASS
- 46.2 Uninstalling Atomix - PASS
- 46.3 Uninstalling ONOS package - PASS
- 46.4 Installing Atomix - PASS
- 46.5 Installing ONOS package - PASS
- 46.6 Set up ONOS secure SSH - PASS
- 46.7 Checking ONOS service - PASS
- 46.8 Starting ONOS CLI sessions - PASS
- 46.9 Checking ONOS nodes - PASS
- 46.10 Checking ONOS applications - PASS
- 46.11 Set logging levels - PASS
- 46.12 Set ONOS configurations - PASS
- 46.13 Starting Mininet Topology - PASS
- 46.14 Check whether the flow count is bigger than 74 - PASS
- 46.15 Check whether all flow status are ADDED - PASS
- 46.16 Check whether the flow count of device of:0000000000000001 is bigger than 37 - PASS
- 46.17 Check whether the flow count of device of:0000000000000002 is bigger than 37 - PASS
- 46.18 Verify full connectivity for [u'h1', u'h2'] with tag CASE46 - PASS
- 46.19 Stopping Mininet - PASS
- 46.20 Copying karaf logs - PASS
Case 47: Bridging test between untagged host and tagged host, with 2x2 leaf-spine topology, ovs switches and 3 ONOS instances -
...
PASS
- 47.1 Apply cell to environment - PASS
- 47.2 Uninstalling Atomix - PASS
- 47.3 Uninstalling ONOS package - PASS
- 47.4 Installing Atomix - PASS
- 47.5 Installing ONOS package - PASS
- 47.6 Set up ONOS secure SSH - PASS
- 47.7 Checking ONOS service - PASS
- 47.8 Starting ONOS CLI sessions - PASS
- 47.9 Checking ONOS nodes - PASS
- 47.10 Checking ONOS applications - PASS
- 47.11 Set logging levels - PASS
- 47.12 Set ONOS configurations - PASS
- 47.13 Starting Mininet Topology - PASS
- 47.14 Check whether the flow count is bigger than 74 - FAIL Flow count looks wrong; found 68, expecting at least 74
- PASS
- 47.15 Check whether all flow status are ADDED - PASS
- 47.16 Check whether the flow count of device of:0000000000000001 is bigger than 37 - FAIL Flow count looks wrong: 17
- PASS
- 47.17 Check whether the flow count of device of:0000000000000002 is bigger than 37 - FAIL Flow count looks wrong: 17
- PASS
- 47.18 Verify full connectivity for [u'h1', u'h2'] with tag CASE47 - FAIL IP connectivity failed
- PASS
- 47.19 Verify full connectivity for [u'h3', u'h4'] with tag CASE47 - FAIL IP connectivity failed
- PASS
- 47.20 Stopping Mininet - PASS
- 47.21 Copying karaf logs - PASS
...
- 75.1 Apply cell to environment - PASS
- 75.2 Uninstalling Atomix - PASS
- 75.3 Uninstalling ONOS package - PASS
- 75.4 Installing Atomix - PASS
- 75.5 Installing ONOS package - PASS
- 75.6 Set up ONOS secure SSH - PASS
- 75.7 Checking ONOS service - PASS
- 75.8 Starting ONOS CLI sessions - PASS
- 75.9 Checking ONOS nodes - PASS
- 75.10 Checking ONOS applications - PASS
- 75.11 Set logging levels - PASS
- 75.12 Set ONOS configurations - PASS
- 75.13 Starting Mininet Topology - PASS
- 75.14 Check whether the flow count is bigger than 28 - PASS
- 75.15 Check whether all flow status are ADDED - PASS
- 75.16 Check whether the flow count of device of:0000000000000001 is bigger than 28 - PASS
- 75.17 Verify full connectivity for [u'h1', u'h2'] with tag CASE75 - PASS
- 75.18 Stopping Mininet - PASS
- 75.19 Copying karaf logs - PASS
Case 76: Bridging test between untagged and tagged hosts with different vlan id, with dual-homed ToR, ovs switches and 3 ONOS instances -
...
PASS
- 76.1 Apply cell to environment - PASS
- 76.2 Uninstalling Atomix - PASS
- 76.3 Uninstalling ONOS package - PASS
- 76.4 Installing Atomix - PASS
- 76.5 Installing ONOS package - PASS
- 76.6 Set up ONOS secure SSH - PASS
- 76.7 Checking ONOS service - PASS
- 76.8 Starting ONOS CLI sessions - PASS
- 76.9 Checking ONOS nodes - PASS
- 76.10 Checking ONOS applications - PASS
- 76.11 Set logging levels - PASS
- 76.12 Set ONOS configurations - PASS
- 76.13 Starting Mininet Topology - PASS
- 76.14 Check whether the flow count is bigger than 74 - PASS
- 76.15 Check whether all flow status are ADDED - FAIL Flow status is wrong!
- PASS
- 76.16 Check whether the flow count of device of:0000000000000001 is bigger than 37 - FAIL Flow count looks wrong: 26
- PASS
- 76.17 Check whether the flow count of device of:0000000000000002 is bigger than 37 - PASS
- 76.18 Verify full connectivity for [u'h1', u'h2'] with tag CASE76 - PASS
- 76.19 Stopping Mininet - PASS
- 76.20 Copying karaf logs - PASS
Case 77: Bridging test between untagged and tagged hosts with different vlan id, with 2x2 leaf-spine topology, ovs switches and 3 ONOS instances -
...
PASS
- 77.1 Apply cell to environment - PASS
- 77.2 Uninstalling Atomix - PASS
- 77.3 Uninstalling ONOS package - PASS
- 77.4 Installing Atomix - PASS
- 77.5 Installing ONOS package - PASS
- 77.6 Set up ONOS secure SSH - PASS
- 77.7 Checking ONOS service - PASS
- 77.8 Starting ONOS CLI sessions - PASS
- 77.9 Checking ONOS nodes - PASS
- 77.10 Checking ONOS applications - PASS
- 77.11 Set logging levels - PASS
- 77.12 Set ONOS configurations - PASS
- 77.13 Starting Mininet Topology - PASS
- 77.14 Check whether the flow count is bigger than 74 - PASS
- 77.15 Check whether all flow status are ADDED - PASS
- 77.16 Check whether the flow count of device of:0000000000000001 is bigger than 37 - PASS
- 77.17 Check whether the flow count of device of:0000000000000002 is bigger than 37 - FAIL Flow count looks wrong: 24
- PASS
- 77.18 Verify full connectivity for [u'h1', u'h2'] with tag CASE77 - PASS
- 77.19 Verify full connectivity for [u'h3', u'h4'] with tag CASE77 - PASS
- 77.20 Stopping Mininet - PASS
- 77.21 Copying karaf logs - PASS
Case 78: Bridging test between untagged and tagged hosts with different vlan id, with 2x4 dual-homed leaf-spine topology, ovs switches and 3 ONOS instances -
...
FAIL
- 78.1 Apply cell to environment - PASS
- 78.2 Uninstalling Atomix - PASS
- 78.3 Uninstalling ONOS package - PASS
- 78.4 Installing Atomix - PASS
- 78.5 Installing ONOS package - PASS
- 78.6 Set up ONOS secure SSH - PASS
- 78.7 Checking ONOS service - PASS
- 78.8 Starting ONOS CLI sessions - PASS
- 78.9 Checking ONOS nodes - PASS
- 78.10 Checking ONOS applications - PASS
- 78.11 Set logging levels - PASS
- 78.12 Set ONOS configurations - PASS
- 78.13 Starting Mininet Topology - PASS
- 78.14 Check whether the flow count is bigger than 212 - PASS
- 78.15 Check whether all flow status are ADDED - PASS
- 78.16 Check whether the flow count of device of:0000000000000001 is bigger than 53 - PASS
- 78.17 Check whether the flow count of device of:0000000000000002 is bigger than 53 - PASS
- 78.18 Check whether the flow count of device of:0000000000000003 is bigger than 53 - PASS
- 78.19 Check whether the flow count of device of:0000000000000004 is bigger than 53 - PASS FAIL
- Flow count looks wrong: 19
- 78.20 Verify full connectivity for [u'h1', u'h2'] with tag CASE78 - PASS
- 78.21 Verify full connectivity for [u'h3', u'h4'] with tag CASE78 - PASS
- 78.22 Stopping Mininet - PASS
- 78.23 Copying karaf logs - PASS